EasyManua.ls Logo

PoolPak ComPak HCD 3500 - HCD;HCDV;HCDH Performance Data

Default Icon
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.poolpak.com | 800-959-772520 | ComPak
®
Series - Installation, Operation and Maintenance
ComPak® HCD (HCDV, HCDH) Performance
Table 3-2. ComPak® HCD Performance Summary
PERFORMANCE AT 82°F AIR AND 80°F WATER
MODEL HCD RETURN AIR CFM
RETURN AIR RH
(%)
MOISTURE REMOVAL
(LBS/HR)
SENSIBLE COOLING
CAPACITY (MBH)
ACC MAX. HEAT
REJECTION (MBH)
0550 900
60 10.2 13.2 30.5
50 7.7 15.2 29.5
0800 1600
60 14.5 20.8 46.2
50 10.3 23.9 44.4
1200 1700
60 19.0 25.2 56.4
50 14.5 28.4 54.4
1400 2300
60 24.1 36.2 74.7
50 17.9 40.5 71.8
1800 2500
60 28.9 41.8 88.1
50 20.9 47.4 84.6
2600 3300
60 41.0 53.5 118.8
50 31.3 59.7 113.8
3500 4300
60 56.9 80.5 169.9
50 41.5 95.2 166.8
4000 4500
60 66.5 86.2 195.3
50 50.2 97.9 187.8

Table of Contents

Related product manuals