EasyManua.ls Logo

PoolPak ComPak HCD 3500 - Detailed Status Menu Navigation

Default Icon
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.poolpak.com | 800-959-772552 | ComPak
®
Series - Installation, Operation and Maintenance
Figure 5-9. Purge Mode Freeze Caution Screen
Detailed Status Menu
To access the detailed status menu:
Press the PRG key to access the main menu.
Use the arrow keys to scroll to the menu selection for Detailed Status and then press the Enter key.
Figure 5-10. Detailed Status Menu
Detailed Status Screen 1 display temperatures:
Surface – The temperature measured at the cold surface sensor.
Dew Point – The calculated dew point of the space.
Dewpt Setpoint – The dew point set point calculated from the temperature and relative humidity set points.
Figure 5-11. Detailed Status Screen 2
Detailed Status Screen 2 display run hours:
Disch Press – The measured refrigerant pressure in the discharge line at the compressor.
Suct Press – The measured refrigerant pressure in the suction line at the compressor.
Suct Temp – The refrigerant temperature measured on the surface of the suction line at the compressor.
Suct SH – The calculated superheat at the suction of the compressor.
Detailed Status Screen 3 display refrigeration system status:
The number of hours the following device or system has been active since power was last applied to the unit:
Cmpr - Compressor
Fan – Supply Fan
A/C – Mechanical Air Cooling (Economizer Cooling Not Included)
Aux – Air – Auxiliary Air Heating
Aux - Wtr – Auxiliary Water Heating

Table of Contents

Related product manuals