EasyManua.ls Logo

PoolPak ComPak HCD 3500 - Changing Set Points; Air Temperature Set Point Adjustment; Relative Humidity Set Point Adjustment

Default Icon
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.poolpak.com | 800-959-772550 | ComPak
®
Series - Installation, Operation and Maintenance
Surf T Sens Fail
Self Diagnostic Fail
10 Fault Lockout
Line 4: Compressor status indication. Possible values include:
Compressor Off
Compressor Running
Compressor Delay Act
Pool T Sens Fail
Outs T Sens Fail
Surf T Sens Fail
Self Diagnostic Fail
10 Fault Lockout
Line 4: Compressor status indication. Possible values include:
Compressor Off
Compressor Running
Compressor Delay ActSet Point Change Menu
Press the PRG key to access the main menu.
Use the arrow keys to scroll to the menu selection for Set Points and then press the Enter key.
Use the arrow keys to select the set point to be changed and then press Enter. Available set points are shown
in the following examples:
AIR TEMPERATURE
Figure 5-6. Air Temperature Selection on the Set Points Menu
Figure 5-7. Air Temperature Set Point Change Screen
For air temperature set point, use the arrow keys to change the set point and then press Enter. The new dew
point set point is shown immediately as DPT. The set point change screen will remain visible for a short time to
allow verification of the new dew point set point. After about five seconds, the RIU will return to the status screen
display.
RELATIVE HUMIDITY
For relative humidity set point, use the arrow keys to change the set point and then press Enter. The new dew
point set point is shown immediately as DPT. The set point change screen will remain visible for a short time to
allow verification of the new dew point set point. After about five seconds, the RIU will automatically return to
the status screen display.

Table of Contents

Related product manuals