www.poolpak.com | 800-959-772586 | ComPak
®
Series - Installation, Operation and Maintenance
DOC# SVW06-STARTUP-20170630
4
___3. Press the PRG (
) button. The screen will show “Main Menu Status Screens”. Press the DOWN
ARROW () until “Main Menu Detailed Status” is displayed and then press ENTER (). Press the
DOWN ARROW () and record the following data:
SURFACE TEMP: °F DISCH PRESS: PSIG
DEWPOINT: °F SUCT PRESS: °F
DEWPOINT SETPOINT: °F SUCT TEMP: °F
SUCT SH: °F
___ 4. If you find any discrepancies between the values recorded above and the actual conditions, please
contact PoolPak Service for assistance.
COMPRESSOR AIR REHEAT MODE
Please note: The Space Air Temp must be above 75
°
F for the compressor to operate. If it is not at
least 75
°
F, allow the auxiliary heat to raise the temperature before proceeding.
___ 1. To place the controller into Demand Control Mode: Press the PRG (
) button. The screen will show
“Main Menu Status Screens”. Press the UP ARROW () to select “Main Menu Service” and then
press the ENTER () button. “Password Required” is displayed. Use the UP ARROW () to change
the number to: 0005 and press the ENTER () button.
Press the UP ARROW () to select “Main Menu Service Manual Mode” and then press the
ENTER () button. “Password Required” is displayed. Use DOWN ARROW () to change the number
to: 9995 and press the ENTER () button. The display should show “Main Menu Service Manual
Mode Demand Control”. Press the ENTER () button.
Press the ENTER () button to move the cursor next to “CMPR HEAT”. Press the UP ARROW () to
change it from NO to YES and press ENTER ().
___ 2. Once the compressor has been operating for at least 10 minutes press the PRG (
) button. The
screen will show “Main Menu Status Screens”. Press ENTER () then press the DOWN ARROW
() and record the following data:
SPACE TEMP: °F OUTSIDE TEMP (Economizer units only): °F
SPACE RH: %
SPACE DEWPOINT: °F POOL TEMP (AW models only) °F
___ 3. Press the PRG (
) button. The screen will show “Main Menu Status Screens”. Press the DOWN
ARROW () until “Main Menu Detailed Status” is displayed and then press ENTER (). Press the
DOWN ARROW () and record the following data:
SURFACE TEMP: °F DISCH PRESS: PSIG
DEWPOINT: °F SUCT PRESS: °F
DEWPOINT SETPOINT: °F SUCT TEMP: °F
SUCT SH: °F