PND Protocol PLX3x Series
User Manual Ethernet and Serial Gateways
Page 214 of 218 ProSoft Technology, Inc.
May 26, 2016
Input Error Message Status
Error code
Description
0
No error
0x0604
Pointer to data memory is NULL
0x0503
Write buffer is already locked or unlocked
0x060A
Data length to be written is invalid
Output Error Message Status
Error code
Description
0
No error
0x0001
No new data was copied into the buffer
0x0604
Pointer to data memory is NULL, or pointer to variable to receive the APDU
Data Status is NULL
0x060B
IOCR ID is 0
0x0803
IOCR ID could not be found, or IOCR ID is invalid
0x060A
Data length to be read is invalid
10.4.3 Configuration Error Codes
The ERR LED is lit when no connection from the PLC is established.
Error Codes
Error code
Description
0
No error
1
Input Swap Error
2
Output Swap Error
18
Get Network Data Adapter
19
Get IP Address Error
20
Get NetMask Error
21
Get Gateway Error
22
Get MAC Address Error
23
PROFINET Mapping Error

Table of Contents