Page 26 
Chapter 4   Programming Guide 
Level
LevelLevel
Level 
  
 
Example 1 Level Measurement  
 
 
 
empty distance (P105), 3.5m  
100%, span (P106), 3.2m   
(output = 5 volts) 
 high alarm on (P213), 2.5m 
 high alarm off (P214), 2.4m 
 low alarm off (P224), 0.6m 
 low alarm on (P223), 0.5m 
0% , empty level (output = 0 volts) 
 
In  this  example,  a  blackbox  and  dB6  is  being  used  to  monitor  a  moving 
level  within  a  vessel  and  is  required  to  provide  a  0  to  5  volt  output 
proportional  to  the  level,  over a  range  of  3.2m.  In addition  when  the  level 
rises to 2.5m, Relay ‘1’ is required to give a high alarm and rest  when the 
level falls to 2.4m. In the event that the level should fall to 0.5m then Relay 
‘2’ is to give a low alarm and reset once the level rise to 0.6m.