Reflexomat with Touch controller ā 06.07.2016 - Rev. B English ā
Pressurisation
Compressor "ON" P
0
+ 0.3 bar Differential pressured added to the "P
0
" minimum
operating pressure.
Compressor "OFF" P
0
+ 0.4 bar Differential pressured added to the "P
0
" minimum
operating pressure.
"Compressor run time exceeded" message 240 minutes The message is displayed after the compressor runs for
240 minutes.
Overflow line "CLOSED" P
0
+ 0.4 bar Differential pressured added to the "P
0
" minimum
operating pressure.
Overflow line "OPEN" P
0
+ 0.5 bar Differential pressured added to the "P
0
" minimum
operating pressure.
Maximum pressure P
0
+ 3 bar Differential pressured added to the "P
0
" minimum
operating pressure.
Filling levels
Insufficient water "ON" 5 %
Insufficient water "OFF" 12 %
Solenoid valve in overflow line "CLOSED" 90 %
Water quantity for each contact 10 litres / contact Optional, if a contact water meter is installed (such as
Fillset Impulse).