Maintenance
56
English Reflexomat with Touch controller06.07.2016 - Rev. B
Activating the device
11. Switch on the main switch.
12. Switch to Automatic mode.
Depending on the filling level and pressure, the "CO" compressor and the automatic make-up will be switched on.
13. Slowly open the cap valves upstream of the tanks and secure them against unintended closing.
Checking Insufficient water "Off"
14. Check the displayed value for the Insufficient water "OFF" filling level message.
Insufficient water "Off" is displayed at the controller at a minimum filling level of 8 %.
Checking Make-up "Off"
15. If necessary, check the make-up value displayed at the controller.
The automatic make-up is deactivated at a level display of 12 %.
Maintenance is completed.
Notice!
If automatic make
-up is not connected, you must manually fill the tanks with water to the recorded filling level.
Notice!
The setting values for pressure maintenance, filling levels and make
-up are provided in the chapter Standard settings, see
chapter
9.3.2 "Default settings" on page 48 .

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reflex Reflexomat Series and is the answer not in the manual?

Reflex Reflexomat Series Specifications

General IconGeneral
BrandReflex
ModelReflexomat Series
CategoryControl Unit
LanguageEnglish

Related product manuals