33
COMMISSIONING AND MAINTENANCE
3.3.2 Burner control and adjustment
ADJUSTING PUMP PRESSURE
Turn the adjuster screw (5) to achieve the pressure setting spec-
ied in the table.
1
2
3
4
5
0
6
5
GITRÈ 4
(*)
GITRÈ 5
GITRÈ 5 B/100
GITRÈ 6
Adjusting pump pressure 12 bar 12 bar 11 bar
(*) Burner with oil heater
ADJUSTING THE AIR DAMPER
The air damper can be adjusted without removing the burner
cover.
− Use an Allen key to turn the adjuster screw (1) to achieve
the required setting on the graduated scale (2)
GITRÈ 4
(*)
GITRÈ 5
GITRÈ 5 B/100
GITRÈ 6
Adjusting the air damper 5,3 3,2 2,5
(*) Burner with oil heater