3.10 Troubleshooting
FAULT CAUSE SOLUTION
The boiler becomes dirty very quickly
Burner badly adjusted
Check adjustment of burner (perform
ue gas analysis)
Blockage in stack Clean ue pipes
Burner air intake dirty Clean the burner air intake
The boiler does not reach its tempera-
ture setpoint
Boiler dirty Clean
Burner capacity insufcient Check and adjust the burner
Problem with boiler control thermostat
Check correct functioning
Check the temperature setting
The generator triggers a thermal safety
block
Problem with boiler control thermostat
Check correct functioning
Check the temperature setting
Check the electrical wiring
Check the position of the sensor bulbs
No water
Check the bleed valve
Check CH circuit pressure
The generator is at temperature but the
heating system is cold
Air in the circuit Bleed the circuit
Pump malfunctioning
Check/unseize the pump
Change the pump
Minimum temperature thermostat faulty
Replace the minimum temperature
thermostat
There is a smell of fumes Fumes escaping into the air
Check that the burner body is clean
Check that the ue pipes are clean
Check the condition of the boiler seals
Check the quality of combustion
The safety valve keeps opening
Incorrect circuit pressure
Check the circuit pressure
Check pressure reducer functioning
Check pressure reducer setting
CH expansion vessel
Check the efciency of the expansion
vessel