Rockwell Automation Publication 1794-UM061B-EN-P - March 2020 75
Configure Your Adapter and Digital Modules on a ControlNet Network        Chapter 6
13. The network and connections are now scheduled.
14. From the main menu, choose Network>Properties. The _default dialog 
appears. 
Specify the following information on network parameters:
15. Specify a value for Network Update Time - the repetitive time interval in 
which data can be sent on the link.
16. Specify a value for Max Scheduled Address - the highest number node that 
has scheduled connections to it.
17. Specify a value for Max Unscheduled Address - the node with the highest 
MAC ID that can use unscheduled time on the link.
These values are set to 99 by default. Change these values to what is 
installed in your system. This saves you time because the controller will not 
have to search for all node addresses.