Rockwell Automation Publication 1794-UM061B-EN-P - March 2020 97
Configure your Digital Module on an EtherNet/IP Network Chapter 7
To use the BOOTP/DHCP utility:
1. Start the BOOTP/DHCP software.
2. Select Tool Network Settings.
If appropriate for your network, enter the subnet mask, gateway address,
primary/secondary server addresses, and roman name. Click OK.
In the Request History panel, you see the hardware addresses of modules
issuing BOOTP requests.
3. Double-click the hardware (MAC) address of the module you want to
configure.
The hardware address is on a sticker that is on the side of the EtherNet/IP
module. The hardware address will be in a format similar to:
00-0b-db-14-55-35.