Rockwell Automation Publication 2715P-UM001C-EN-P - March 2019 23
Install the PanelView 5510 Terminal Chapter 2
The terminals have a temperature code of T4 when operating in a 55 °C
(131 °F) maximum ambient temperature. Do not install product in environments
where atmospheric gases have ignition temperatures less than 135 °C (275 °F).
North American Hazardous Locations
The following information applies when operating this
equipment in hazardous locations.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
ATTENTION: When marked, these products are suitable for use
in “Class I, Division 2, Groups A, B, C, D”; Class I, Zone 2, Group IIC
hazardous locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When
combining products within a system, the most adverse
temperature code (lowest T” number) be used to help
determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the
time of installation.
ATTENTION: Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne
conviennent qu'à une utilisation en environnements de Classe I
Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être utilisé
pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de
l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.
Substitution of components impair suitability
for Class I, Division 2.
Peripheral equipment must be suitable for the
location in which it is used.
The battery in this product must be changed
only in an area known to be nonhazardous.
All wiring must be in accordance with Class I,
Division 2 wiring methods of Article 501 of the
National Electrical Code and/or in accordance
with Section 18-1J2 of the Canadian Electrical
Code, and in accordance with the authority
having jurisdiction.
AVERTISSEMENT: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.
Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
Les équipements périphériques doivent
s'adapter à l'environnementdans lequel ils sont
utilisés.
S'assurer que l'environnement est classé non
dangereux avant de changer la pile ou le module
horloge temps réel de ce produit.
Tous les systèmes de câblage doivent être de
Classe I, Division 2, conformément aux méthodes
de câblage indiquées dans les Articles 501 du
National Electrical Code (Code Electrique
National) et/ou conformément à la Section 18-
1J2 du Canadian Electrical Code (Code Electrique
Canadien), et en fonction de l'autorité de
jurisdiction.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PanelView 5510 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PanelView 5510 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PanelView 5510 Series
CategoryTouch terminals
LanguageEnglish

Related product manuals