Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 74 of 79
0427,
0428
FP register R/W, WP Sensor lim-
its
SP lower operating limit
0429,
0430
FP register RO PT upper range limit
0431,
0432
FP register RO PT lower range limit
0433,
0434
FP register R/W, WP PT upper operating limit
0435,
0436
FP register R/W, WP PT lower operating limit
0437,
0438
FP register R/W, WP DP calibra-
tion
DP offset
0439,
0440
FP register R/W, WP DP slope
0441,
0442
FP register R/W, WP DP damping
0443,
0444
FP register R/W, WP SP calibra-
tion
SP offset
0445,
0446
FP register R/W, WP SP slope
0447,
0448
FP register R/W, WP SP damping
0449,
0450
FP register R/W, WP PT calibra-
tion
PT offset
0451,
0452
FP register R/W, WP PT slope
0453,
0454
FP register R/W, WP PT damping
0455,
0456
FP register R/W, WP User
Entered PT
User Entered PT Value