Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 49 of 79
7.0 LCD Display Configuration
If the 3095FB includes an optional LCD display, the user may select which configuration
parameters to display. This is accomplished by the use of the display bit map. The rate at which
the LCD display is updated is also configurable between one and ten seconds.
Table 7-1 Transmitter Info
Modbus Access
DESCRIPTION
Address
Address
Type
Attributes
Functional
Area
Data / Control
0126 Holding
register
R/W, WP LCD LCD Update Rate (1 - 10 seconds)
0127,
0128
Holding
register
R/W, WP LCD Display Bit Mask
0x0000 0001
0x0000 0002
0x0000 0004
0x0000 0008
Differential Pressure
Static Pressure
Process Temperature
Communication Setup
*Attributes: R/W = Read/Write, RO = Read Only, WP = Write Protected
**These registers are available at multiple Modbus addresses (see Section 2.3
located in the Modbus Protocol Guide)