Reference Manual
00809-0100-4738, Rev DA
May 2006
Rosemount 3095FB
www.rosemount.com
Appendix A Specifications and
Reference Data
FUNCTIONAL
SPECIFICATIONS
Service
Gas, Liquid, or Steam
Differential Sensor
Limits
Code 2: –250 to 250 inH
2
O (-0,622 to 0,622 bar)
Code 3: –1000 to 1000 inH
2
O (-2,49 to 2,49 bar)
Absolute Sensor
Limits
Code 3: 0.5 to 800 psia (3,447 to 5516 kPa)
Code 4: 0.5 to 3,626 psia (3,447 to 25000 kPa)
Gage Sensor
Limits
•Code C: 0 to 800 psig (0 to 5516 kPa)
Code D: 0 to 3,626 psig (0 to 25000 kPa)
Over Pressure Limit
0.5 psia to two times the absolute pressure sensor range with a maximum of 3,626 psia.
Static Pressure Limit
Operates within specifications between static line pressures of 0.5 psia and the URL of the
absolute pressure sensor.
Power
Quiescent supply current 10 mA typical. Transmitting supply current not to exceed 100 mA.
External power supply required
Transmitter: operates on terminal voltage of 7.5 - 42 Vdc
RS-485 Signal Wiring
2-wire half-duplex RS-485 MODBUS with 8 data bits, 1 stop bit,
and no parity
Bus Terminations
Standard RS-485 bus terminations required per EIA-485.
Failure Mode Alarm
If self-diagnostics detect a gross transmitter failure, non-latched status bits are set in the
transmitter alarm registers.
Humidity Limits
0 – 100% relative humidity
Communications
User Interface: EIA-232 (RS-232C) format
Baud Rate: 600 to 19.2 K User selectable
Host: RS-485 / RS-232