Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 26 of 79
4.2 Transmitter Info
Table 4-1 Transmitter Info
Modbus Access
DESCRIPTION
Address
Address
Type
Attributes
Functional
Area
Data / Control
0017 Input Reg-
ister
RO Materials
of Con-
struction
DP Sensor Range Code (U8)
2
3
-250 to 250 in H
2
O @ 60 F
-830 to 830 in H
2
O @ 60 F
0018 Input Reg-
ister
RO SP Sensor Range Code (U8)
3
4
0 to 800 psi
0 to 3,626 psi
0019 Input Reg-
ister
RO PT Sensor Range Code (U8)
2 -40 to 1200 F
0020 Input Reg-
ister
RO Module Isolator Code (U8)
2
3
4
5
15
253
316 Stainless Steel
Hastelloy C
Monel
Tantalum
Gold/Monel
Special
0021 Input Reg-
ister
RO Module Fill Fluid Code (U8)
1
2
250
253
Silicone
Inert
Not Used
Special
0022 Holding
register
R/W, WP flange material code (U8)
0
2
3
4
24
252
253
Carbon Steel
316 Stainless Steel
Hastelloy C
TM
Monel
Kynar
Unknown
Special