Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 18 of 79
Function 16: Writing Floating Point Data in a 32-bit Register
Address Function Starting
register
# of reg-
isters
byte
count
Register
data bytes
Error
check
Query 01 10 1C F0 00 01 04 43 66 00 00 XXXX
Address Function Starting
register
# of reg-
isters
Error
check
Response 01 10 1C F0 00 01 XXXX
Function 70: Writing Floating Point Data using a 32-bit Function
Address Function Starting
register
# of reg-
ister
pairs
byte
count
Register
data bytes
Error
check
Query 01 46 01 A0 00 01 04 43 66 00 00 XXXX
Address Function Starting
register
# of reg-
isters
pairs
Error
check
Response 01 46 01 A0 00 01 XXXX