COMEO - INSTALLATION INSTRUCTIONS
III- 65
Motor Power (kW) Net voltage Protection Max. cable length (m) Wire gauge (mm²)
1.5
1x230V 50Hz GV2ME14
0-27 1.5
28 - 46 2.5
47 - 74 4
3x230V 50Hz GV2ME10
0-44 1.5
45 - 73 2.5
74 - 117 4
3x400V 50Hz GV2ME08
0-123 1.5
124 - 205 2.5
206 - 328 4
1.8
3x220V 60Hz
3x230V 60Hz
GV2ME14
0-26 1.5
27 - 44 2.5
45 - 71 4
3x380V 60Hz
3x400V 60Hz
GV2ME10
0-74 1.5
75 - 124 2.5
125 - 199 4
2.2
3x230V 50Hz GV2ME14
0-27 1.5
28 - 46 2.5
47 - 74 4
3x400V 50Hz GV2ME10
0-78 1.5
79 - 130 2.5
130 - 208 4
2.64
3x380V 60Hz
3x400V 60Hz
GV2ME14
0-47 1.5
48 - 78 2.5
79 - 125 4
In reality, if the cable lengths are longer than the ones given in the tables above, then you have to take one of
the following actions:
Double the section of the PE (earth connection)
Increase the section of the phases AND the PE (earth connection)
Place a earthleak circuit breaker