The following data can be configured:
n 4mA signal (zero level value) Enter the zero level of the connected sensor, corresponding to its 4mA level, in
this eld.
n 20mA signal (full scale level value) Enter the full scale level of the connected sensor, corresponding to its
20mA level, in this eld.
n Units of measure Enter the connected sensor units of measure, ie %RH for a humidity sensor.
n Alarm activation level The level at which an alarm needs to be activated is entered in this eld.
n Hysteresis Enter the hysteresis level, below or above (depending on the activation direction)
the activation level at which the alarm will be de-activated. (Ref. note 1, pg 31)
n Alarm activation direction Select the alarm activation direction, ie increasing values or decreasing values.
n Sampling period Select the sampling period at which the sensor is sampled for display on the
Graph View. A maximum of 1 440 sample points are stored.
Select Save to store data on the unit after all elds have been congured. Select Cancel and follow the prompted instructions to revert
back to the previous settings. The data will not be stored in this case.