28
The following data can be configured:
n 4mA signal (zero level value) Enter the zero level of the connected sensor, corresponding to its 4mA level, in
this eld.
n 20mA signal (full scale level value) Enter the full scale level of the connected sensor, corresponding to its
20mA level, in this eld.
n Units of measure Enter the connected sensor units of measure, ie %RH for a humidity sensor.
n Alarm activation level The level at which an alarm needs to be activated is entered in this eld.
n Hysteresis Enter the hysteresis level, below or above (depending on the activation direction)
the activation level at which the alarm will be de-activated. (Ref. note 1, pg 31)
n Alarm activation direction Select the alarm activation direction, ie increasing values or decreasing values.
n Sampling period Select the sampling period at which the sensor is sampled for display on the
Graph View. A maximum of 1 440 sample points are stored.
Select Save to store data on the unit after all elds have been congured. Select Cancel and follow the prompted instructions to revert
back to the previous settings. The data will not be stored in this case.