19
SYSTEM STARTUP—PARAMETERS
P. 1 45 0 – 30% Torque boost – door-close cycle 0
P. 2 10 0 – 5 Limit setup
0: off
1: open, close, and partial setup (partial set using P.244)
2: open
3: open and close
4: partial (P.244 ignored)
5: all (partial set using P.244)
0
P. 2 21 ±125 increments Close limit adjustment
(For minor adjustments to the close position of the door. This
adjustment resets to 0 if the limits are reset.)
0
P. 2 31 ±60 increments Open limit adjustment
(For minor adjustments to the open position of the door. This
adjustment resets to 0 if the limits are reset.)
0
P. 2 32 0 – 2100 Deceleration distance 400
P. 2 44 0 – 3 Partial position
0: parameter off
1: half-open position
2: two-thirds-open position
3: operator-established position
0
P. 3 10 6 – 200 Hz Frequency setting (opening) – controls door-open speed 60
P. 3 50 6 – 200 Hz Frequency setting (closing) – controls door-close speed 40
P.5B0 – P.5B9 Input 11 – programmable
P.5C0 – P.5C9 Input 12 – programmable
P. 6 30 0 – 2 Up (
) key function
0: off in run mode – on in operator/service modes
1: on only in jog open
2: on in all functions
2
P. 6 33 0 – 3 Open position – when door is activated with up (
) key
0: full-open position
1: partial position
2: press up (
) key one time to move door to partial position,
press up (
) key a second time to move to full-open position
3: press up (
) key twice to move door to full-open position
P. 6 34 0 – 2 Auto-close delay timer – activated with up (
) key
0: none
1: ACL1
2: ACL2
1
P. 6 35 0 – 1 Delay to open/close timer – activated with up (
) key
0: off
1: on
1