EasyManua.ls Logo

SAJ Suntrio-TL Series - Page 52

SAJ Suntrio-TL Series
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual
User Manual
User Manual
49
Error Code
LCD Display
Message
Phenomenon and Possible Cause
Phenomenon and
Possible Cause
73 L1 No Grid Err S
The connec tion betw een Grid and
inverter has problems or is missing.
Chec k the AC con nection.
I f ev e r y t h i n g i s c o r r e c t ,
you ne ed t o co ntact loc al
agent or SAJ Service line.
74 L2 No Grid Err S
75 L3 No Grid Err S
76 PV1 Volt High S
1)The open-circuit voltage of the PV
generator is higher than the maximum
DC inpu t vo lt age o f th e i nv erter.
C h e c k t h e P V s t r i n g
c o n f i g u r a t i o n . T h e S A J
D e s i g n e r c a n h e l p y o u .
I f ev e r y t h i n g i s c o r r e c t ,
you ne ed t o co ntact loc al
agent or SAJ Service line.
77 PV2 Volt High S
78 PV1 Curr. High S
1)The PV inp ut current is beyond
the Max. Input Current. The value is
specied in the datasheet of the inverter.
2)The internal current sensor is damaged.
If the e rro r is stil l active,
p l e a s e co n t a c t t h e l o c a l
agent or SAJ Service line.
79 PV2 Curr. High S
80 PV Voltage Low S The voltage of the PV input is too low.
C h e c k t h e P V s t r i n g
c o n f i g u r a t i o n . T h e S A J
D e s i g n e r c a n h e l p y o u .
I f ev e r y t h i n g i s c o r r e c t ,
you ne ed t o co ntact loc al
agent or SAJ Service line.
81 Lost Com. D<->C D
Communication between Control board
and Display board fails.
Check the connection between
Control board and Display
board. If everything is correct,
you ne ed t o co ntact loc al
agent or SAJ Service line.
2)Sudden DC surge.