EB 5824-2 EN 6-5
Operation
6.1.3 Function switch
Thefunctionswitchhasthefollowingfunctions:
1. Determining the input signal range
2. Startinginitialization(seethe'Start-upandconguration'section).
− SwitchpositionA(default):
Î Inputsignal0to10Vor0to20mA
Î Input signal settings in TROVIS-VIEW are taken into account.
− SwitchpositionB:
Î Inputsignal2to10Vor4to20mA
Î Input signal settings in TROVIS-VIEW are ignored.
FunctionswitchinType5824(24Vversion)
FunctionswitchinType5824(85to264Vversion)
Function switch with
switchpositions:
B
A
Function switch with
switchpositions:
B
A