EB 5824-2 EN 17-3
Annex B
17.3 Congurationlistandcustomer-specicdata
Conguration
Default setting
Adjustment range Setting
Input signal
Lower range value
0.0V
0.0mA
0.0to7.5V
0.0to15.0mA
Upper range value
10.0V
20.0mA
2.5to10.0V
5.0to20.0mA
Unit V V/mA
Position feedback signal
Lower range value 0.0V 0.0to10.0V
Upper range value 10.0V 0.0to10.0V
Functions
Detect input signal failure No Yes/No
Positioning value upon input signal
failure
Internal Internal/last position
Internal positioning value 0.0% 0.0to100.0%
Value above limit (end position
guiding)
1.0% 0.0to49.9%
Value below limit (end position
guiding)
97.0% 50.0to100.0%
Blocking protection No Yes/No
Limited travel range 100.0% 30.0to130.0%
Travel adjustment Absolute Absolute/Relative
Velocity Standard Slow/Standard/Fast
Dead band (switching range) 2.0% 0.5to5.0%
Characteristic type Linear
Linear
Equal percentage
Reverse equal percentage
User-dened