EasyManua.ls Logo

Samson 5824 - Position Feedback Signal; Functions; Detect Input Signal Failure

Samson 5824
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16-2 EB 5824-2 EN
AnnexA(congurationinstructions)
16.2 Position feedback signal
The position feedback indicates the position of the actuator stem.
The span of the position feedback signal is adjusted over the lower and upper range value
parameters.
Settings\Inputs and outputs\Position feedback signal
Position feedback signal WE Adjustment range
Lower range value 0.0V 0.0Vto10.0V
Upper range value 10.0V 0.0Vto10.0V
16.3 Functions
16.3.1 Detect input signal failure
The positioner detects a failure of the input signal as soon as the value falls below the lower
rangevalueby0.3Vor0.6mA.Aninputsignalfailureisindicatedinthe'Service'folder
('Errors') as well as by the red LED:
− Input signal failure detected
On
Off
Time in s
The input signal failure can only be detected when at least 0.5V or 1mA is set as the lower
range value.
If the 'Detect input signal failure' function is active, the reaction of the actuator upon failure
of the input signal is determined by the Positioning value upon input signal failure parame-
ter.
− 'Positioning value upon input signal failure' = Internal
Theactuatorstemmovestothepositionspeciedinthe'Internalpositioningvalue'pa-
rameter upon failure of the input signal.
Note

Table of Contents