Samson TROVIS 5579 - Sending Text Messages in Case of Error

Samson TROVIS 5579
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Error message Meaning Decimal value
Err 1 Sensor failure 111
Err 2 2
Err 3 Disinfection temperature not reached 4
Err 4 Maximum charging temperature reached 8
Err 5 Error message issued by device bus 16 16
Err 6 Temperature monitor alarm 32
Err 7 Unauthorized access occurred 64 64
Err 8 Error message of a binary input 128 128
Err 9 Meter bus communication error 256 256 256
Err 10 Error message issued by heat meter 512
Total Total
Default setting range after entering the key number 0025 = 465
Example: Value of error status register when a sensor fails and
a meter bus communication error occurs =
257
8.6 Sending text messages in case of error
If a dial-up modem is connected to the RS-232 system bus interface, the controller can send
a text message to a mobile phone when an error occurs.
As soon as a fault has been registered in the error status register, the text message indicating
a controller fault is sent. On the mobile phone, the following error message is displayed:
The time stamp [Date], [Time] is added by the text messaging center, not by the controller. If
an error message is transmitted over the device bus to a controller equipped with a dial-up
modem, the controller ID of the faulty controller is sent, instead the controller ID of the “mo-
dem controller”. A detailed error message is not available.
116 EB 5579 EN
Operational faults
[Date] [Time]
[Phone no. of the controller]
Controller fault
TROVIS 5579 # [controller ID of the faulty controller]