1.9 Setting room and DHW temperature set points
For the heating circuits, the required room temperatures during the day (
Day set point
) and
during the night (
Night set point
) can be set.
In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
The temperature set points for the different control circuits are set at the rotary switches one
after the other:
Desired temperature set point Switch Position
Heating circuit 1*: Day set point Top
Heating circuit 1*: Night set point Top
Heating circuit 2*: Day set point Middle
Heating circuit 2*: Night set point Middle
DHW heating*: DHW temperature set point Bottom
Heating circuit 3*: Day set point
DHW heating*: DHW temperature sustained value Bottom
Heating circuit 3*: Night set point
* Refer to page 161 for assignment
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle / 0 to 40 °C
Night set point 15 °C Top, middle / 0 to 40 °C
DHW temperature set point 55 °C Bottom / Min. to max. DHW temperature
Proceed as follows:
Turn appropriate rotary switch to “Set point temperature“.
Display shows: temperature
q
Set temperature value.
Return the rotary switch to the required operating mode (left side).
20 EB 5579 EN