EasyManua.ls Logo

Samson TROVIS 5579 - System Bus Interface with RS-232;RS-485 Cable Converters (for Two-Wire and Four-Wire Bus)

Samson TROVIS 5579
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters*
WE Parameter level / Range of values
Station address (ST.-NR) 255 PA6 / 1 to 247 with CO6 -> F02 - 1: 1 to 32000
Baud rate (BAUD) 9600 PA6 / 19200, 9600
Cyclical initialization (I) 30 min PA6 / 1 to 255 min
Modem dialing pause (P) 5 min PA6 / 0 to 255 min
Modem time-out (t) 5 min PA6 / 1 to 255 min
No. of redialing attempts (C) 5 PA6 / 1 to 255
Phone no. of control station (tELnr) PA6 / Max. 22 characters; 1, 2, 3, …9, 0;
“-“ end of a string, “P“ pause
* –> section 9.3 (Description of communication parameter settings)
9.2 System bus interface with RS-232/RS-485 cable converters
(for two-wire and four-wire bus)
To operate the controller in combination with cable converters, a constant bus connection is
required (data cable). The bus line links the control units/devices in an open ring. At the end
of the bus line, the data cable is connected to the control station using an RS-485/RS-232
converter (e.g. TROVIS 5484).
The maximum range of the bus connection (cable length) is 1,200 meters. A maximum of
126 devices (two-wire bus) can be connected to such a segment.
If you wish to use more than 126 devices in line or need to bridge greater distances, make
sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit address-
ing, a maximum of 246 devices can be addressed and connected to a bus.
If there is no communication between the control system and the controller, interventions of
120 EB 5579 EN
Communication
1
2
3
4
5
6
7
8
Device bus
Device bus
+5V
RD
CTS
DTR
TD
GND
Fig. 14 · Assignment of the RJ-45 jack

Table of Contents

Related product manuals