Samson TROVIS 5579 - Flash Adaptation Without Outdoor Sensor (Room Temperature Dependent)

Samson TROVIS 5579
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
WE Configuration
Room sensors RF1/2/3 0 CO1, 2, 3 -> F01 - 1
Flash adaptation 0
20 min
0
CO1, 2, 3 -> F09 - 1
Cycle time / 1 to 100 min
K
P
(gain) / 0 to 25
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle, bottom/0to4C
Night set point 15 °C Top, middle, bottom/0to4C
5.8.1 Flash adaptation without outdoor sensor (room temperature
dependent)
The flow temperature control starts with
Flow day set point
in rated operation or with
Flow
night set point
in reduced operation as no set points calculated using characteristics exist
without an outdoor sensor. The
Cycle time
determines the intervals at which the flow temper-
ature set point is corrected by 1 °C. The heating is then always switched off as soon as the
room temperature exceeds the
Day set point
or
Night set point
by 2 °C. Heating first starts
again when the room has cooled off and the room temperature is 1 °C above the
Set point
.
A
Gain K
P
set to a value other than 0 causes a direct increase/decrease in flow temperature
set point when a sudden deviation in room temperature arises. A
Gain K
P
setting of 10.0 is
recommended.
Functions
WE Configuration
Room sensors RF1/2/3 0 CO1, 2, 3 -> F01 - 1
Outdoor sensor AF1/2 1 CO1 (2, 3) -> F02 - 0
Flash adaptation 0
20 min
0
CO1, 2, 3 -> F09 - 1
Cycle time / 1 to 100 min
K
P
(gain) / 0 to 25
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle, bottom/0to4C
Night set point 15 °C Top, middle, bottom/0to4C
Parameters
WE Parameter level / Range of values
Flow day set point 50 °C PA1, 2, 3 / 5 to 130 °C
Flow night set point 30 °C PA1, 2,3/5to13C
80 EB 5579 EN
Functions of the heating circuit