CO1: Heating circuit Rk1 (not system Anl 1.9)
F Function WE Anl
Comment
Function block parameters / Range of values (default)
01 Room sensor RF1 0 Not in Anl
1.5-1.8,
3.x, 5.x,
7.x, 9.x,
12.x
CO1 -> F01 - 1: Temperature display and input FG1 for
Type 5244/5257-5 Room Panel active
TROVIS 5570 Room Panel:
CO1 -> F01 - 1 and CO7 -> F03 - 1
02 Outdoor sensor
AF1
1 Not in Anl
1.5-1.8,
7.x
CO1 -> F02 - 1: Weather-compensated control active
Outdoor temperature received via device bus:
CO1 -> F02 - 1 and CO7 -> F07 - 1
03 Return flow sensor
RüF1
0 1.2, 1.4,
10.2, 21.1
CO1 -> F03 - 1: Sensor and limiting function active
Function block parameter:
Limiting factor / 0.1 to 10.0 (1.0)
1 Not in Anl
1.2, 1.4,
10.2, 21.1
04 Reserved
05 Underfloor heating
Drying of jointless
floors
0 Not in Anl
1.5-1.8,
3.x, 7.x,
9.x, 12.x
CO1 -> F05 - 1: Limitation of the adjustment ranges
Function block parameters:
Start temperature / 20 to 60 °C (25 °C)
Temperature rise / 1 to 10 °C/24 h (5 °C/24 h)
Maximum temperature / 25 to 60 °C (45 °C)
Maintaining time of max. temperature/1 to 10 days (4 days)
Temperature reduction / 0 to 10 °C/ 24 h (0 °C / 24 h)
n
START,
nn
START,
nnn
START
06 Reserved
07 Optimization 0 Not in Anl
1.5-1.8,
3.x, 5.x,
7.x, 9.x,
12.x
CO1 -> F07 - 1: Only with • CO1 -> F01 - 1
• CO1 -> F02 - 1
08 Adaptation 0 Not in Anl
1.5-1.8,
3.x, 7.x,
9.x, 12.x
CO1 -> F08 - 1: Only with • CO1 -> F01 - 1
• CO1 -> F02 - 1
• CO1 -> F11 - 0