F Function WE Anl
Comment
Function block parameters / Range of values (default)
09 Flash adaptation 0 Not in Anl
1.5-1.8,
3.x, 7.x,
9.x, 12.x
CO1 -> F09 - 1: Only with CO1 -> F01 - 1
Function block parameters:
Cycle time / 1 to 100 min (20 min)
K
P
(gain) / 0 to 25 (0)
10 Reserved 0
11 4-point
characteristic
0 Not in Anl
1.5-1.8,
3.x, 7.x,
9.x, 12.x
CO1 -> F11 - 1: 4-point characteristic,
only with CO1 -> F08 - 0
CO1 -> F11 - 0: Gradient characteristic
12 Control mode
three-step [Rk1]
0 to 10 V [Y1]
1 All CO1 -> F12 - 1:With [Rk1] three-step control
With [Y1] 0 to 10 V control
Function block parameters:
K
P
(proportional gain) / 0.1 to 50.0 (2.0)
T
N
(reset time) / 1 to 999 sec (120 sec)
T
V
(derivative-action time) / 0 to 999 sec (0 sec)
T
Y
(valve transit time) / 5, 10, 15, ..., 240 sec (45 sec)
CO1 -> F12 - 0: On/off control
Function block parameters:
Hysteresis / 1 to 30 °C (5 °C)
Min. ON time / 0 to 10 min (2 min)
Min. OFF time / 0 to 10 min (2 min)
13 Limitation of
deviation for OPEN
signal
0 All CO1 -> F13 - 1: Only with CO1 -> F12 - 1
Function block parameter:
Max. deviation / 2 to 10 °C (2 °C)
14 Release Rk1
at BE15
0 All With CO1 -> F14 - 1, FG1 has no function;
Options bE / 1, 0 (1)
15 Processing of
external demand
in Rk1
0 All How the external demand is processed in Rk1 depends on
CO1 -> F16, CO1 -> F17 and CO7 -> F15.
16 Processing of
external demand,
0 to 10 V
Input term. 17/19
0 Not in
systems with
solar circuit
or room
panel
RF3/FG3
CO1 -> F16 - 1: Only with CO1 -> F15 - 1
CO1 -> F17 - 0
134 EB 5579 EN
Appendix