Functions
WE Configuration
Meter bus 0
255
1434
24h
CO6 -> F10 - 1
Meter bus address WMZ 1 to 6 (ST.-NR) / 0 to 255
Model code WMZ 1 to 6 / 1434, CAL3, APAtO, SLS
Reading mode WMZ 1 to 6 / 24h, CONT, CoiL
Capacity limitation in Rk1 using
meter bus
0
1.5 kW
1.5 kW
1.5 kW
1.0
CO6 -> F12 - 1
Max. limit value* / 0.01 to 6500 kW
Max. limit value for heating / 0.1 to 6500 kW
Max. limit value for DHW / 0.1 to 6500 kW
Limiting factor / 0.1 to 10.0
* Icons of the maximum limit values on the display:
System –> “Flow rate“ and “Fixed set point“
Heating –> “Flow rate“, “Fixed set point“ and “Radiator“
DHW –> “Flow rate“, “Fixed set point“ and “Tap“
126 EB 5579 EN