Functions
WE Configuration
Pump management –
switching states of BA13 *
0 CO5 -> F17 - 1: Speed control released with BA13 = ON
CO5 -> F17 - 0: Speed control released with BA13 = OFF
Fault indication output
BA13
0 CO5 -> F07 - 0
BA12 ON during thermal
disinfection
0 CO4 -> F17 - 0
BA12 ON during DHW
demand
CO4 -> F18 - 0
* CO5-> F17 - 0 or -1 only influences the switching state of binary output BA13!
Note: If CO5 -> F07 - 1, CO4 -> F17 - 1 or CO4 -> F18 - 1 is configured, the pump
management function is no longer available.
82 EB 5579 EN