5. Parameters 5-73
5.8.5.2 Output terminal function during fault retry : P4.02
Parameter
No.
Name Unit
Setting
range
Factory
Setting
Changeab
le during
operation
P4.02
Output Terminal
Function at Retry
- 0~1 0 X
P4.02 can be used when the multi-function output terminal setting
function is ‘default output’ (H1.01)
• Setting
Setting
constant
Function
0 Do not output fault restart (fault contact does not operate)
1 Output fault restart (fault contact operates)
5.8.5.3 Fan error : P5.01
Parameter
No.
Name Unit
Setting
range
Factory
Setting
Changeable
during
operation
P5.01 Fan Error - 0~1 0 X
P5.02 can be used to enable or disable the fan error detecting function.
• Setting
Setting
constant
Function
0 Enabled (fan error is detected)
1 Disabled (fan error is not detected)
5-74 MOSCON-E7 User’s Manual
5.9 Error Monitoring
Information on the previous error can be monitored from U1 and U2
• U1-displays the information on the last error.
• U2-displays up to last four errors.
(refer to parameter description for more details)