Chapter 4 PAS Application Software
Viewing Recorded Files
Series PM175 Powermeters
127
The standard compliance statistics is reported within the
selected time range on a daily, weekly or yearly basis
depending on the observation periods stated in the EN50160
for voltage characteristics. If the time range includes a number
of the observation intervals, each interval’s statistics is given in
a separate row. For power frequency, both weekly and yearly
compliance statistics are provided.
For characteristics provided with definite limits, the report
shows a percentage of the observation time within which the
characteristic complied with the standard, e.g. 98% of the
observations in a period of one week, and the total compliance
indicator.
For voltage characteristics provided with indicative values, the
report gives the yearly statistical data classified by voltage
magnitude and duration.
Selecting the Report Time Range
To change the time range or contents of the report, click on
the report with the right mouse button, select “Options…”,
select the required time range, check the voltage
characteristics to be included in the report, and then click OK.