5A secondary
Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 300A RMS for 1
second
1A secondary
Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 6A RMS continuous, 80A RMS for 1
second
Relay Outputs
2 relays rated at 3A/250 VAC; 3A/30 VDC, 2 contacts (SPST
Form A)
Wire size: 14 AWG (up to 1.5 mm
2
)
Galvanic isolation:
Between contacts and coil: 2000 VAC 1 min
Between open contacts: 1000 VAC
Operate time: 10 ms max.
Release time: 5 ms max.
Update time: 1 cycle
Digital Inputs
2 Digital Inputs Dry Contacts
Wire size: 14 AWG (up to 1.5 mm
2
)
Galvanic isolation: 2000V RMS
Internal power supply 15V
Scan time: 1 ms
Optional Analog Inputs
2 Analog Inputs (optically isolated)
Ranges (upon order):