EasyManua.ls Logo

Satec PM175 - Page 141

Satec PM175
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A Technical Specifications
Series PM175 Powermeters
141
5A secondary
Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 300A RMS for 1
second
1A secondary
Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 6A RMS continuous, 80A RMS for 1
second
Relay Outputs
2 relays rated at 3A/250 VAC; 3A/30 VDC, 2 contacts (SPST
Form A)
Wire size: 14 AWG (up to 1.5 mm
2
)
Galvanic isolation:
Between contacts and coil: 2000 VAC 1 min
Between open contacts: 1000 VAC
Operate time: 10 ms max.
Release time: 5 ms max.
Update time: 1 cycle
Digital Inputs
2 Digital Inputs Dry Contacts
Wire size: 14 AWG (up to 1.5 mm
2
)
Galvanic isolation: 2000V RMS
Internal power supply 15V
Scan time: 1 ms
Optional Analog Inputs
2 Analog Inputs (optically isolated)
Ranges (upon order):
1 mA (100% overload)
0-20 mA
4-20 mA
0-1 mA (100% overload)
Wire size: 14 AWG (up to 1.5 mm
2
)
Isolation: 2,000 V RMS
Accuracy: 0.5% FS
Scan time: 1 cycle
Optional Analog Outputs
2 Analog Outputs (optically isolated)
Ranges (upon order):
1 mA, maximum load 5 k
(100% overload)
0-20 mA, maximum load 510
4-20 mA, maximum load 510
0-1 mA, maximum load 5 k
(100% overload)
Isolation: 2,000 V RMS
Power supply: internal
Accuracy: 0.5% FS
Wire size: 14 AWG (up to 1.5 mm
2
)
Update time: 1 cycle

Table of Contents

Related product manuals