Page #85 background imageLoading...
Page #85 background image
Chapter 4 PAS Application Software
Configuring Summary Energy and TOU Registers
Series PM175 Powermeters
85
The meter’s TOU calendar allows you to configure any tariff
schedule based on any possible utility regulation. The
calendar itself has 32 entries that allow you to specify profiles
for working days and holidays through all seasons in any order
that is convenient for you, based on simple intuitive rules.
There are no limitations on how to define your schedule. The
meter is able to automatically recognize your settings and to
select a proper daily tariff schedule for any day within a year.
The above picture gives you an example of a single-season
tariff schedule configured for weekends and the designated
U.S.A. holidays.
To configure your season tariff schedule:
1. In the “Season” box, select the season, and in the “Day
Type” box, select a day type for this calendar entry.
2. Select the time interval when this daily tariff schedule is
effective, based on the start and the end weekdays and,
for a multi-season schedule, on the start and the end
month for the selected season. It does not matter which
order of weekdays or months you select: the meter
recognizes the correct order.
3. For exception days like designated holidays, select a
specific day either by specifying a day and month, or by
selecting a month, a week and a weekday within the
month.