46 CSP-204 ● CSP-208 ● CSP-104 ● CSP-108 SATEL
12. Specifications
12.1 Control panels
Main power supply .......................................................................230 V AC +10%, -15% 50 Hz
Maximum mains current consumption............................................................................... 0.5 A
Power supply overcurrent protection....................................................... slow-blow fuse 3.15 A
Current parameters of integrated power supply (acc. to EN54-4):
Imax a .............................................................................................................. 2.5 A
Imax b .............................................................................................................. 3.6 A
Backup power supply:
internal lead-acid battery...................................12 V / 17 Ah e.g. HV17-12W KOBE
external lead-acid battery................................12 V / ≤24 Ah e.g. HP24-12W KOBE
Backup battery life .............................................................................................................. 72 h
Battery charging current, max ........................................................................................... 1.4 A
Battery charging system overcurrent protection........................................ slow-blow fuse 3.5 A
Maximum battery internal resistance (with wires and terminals in circuit) ............................ 1 Ω
Current consumption from battery – quiescent condition:
CSP-208 .......................................................................................................140 mA
CSP-204 .......................................................................................................100 mA
CSP-108 .......................................................................................................140 mA
CSP-104 .......................................................................................................100 mA
Current consumption from battery – fire alarm condition:
CSP-208 .......................................................................................................215 mA
CSP-204 .......................................................................................................170 mA
CSP-108 .......................................................................................................215 mA
CSP-104 .......................................................................................................170 mA
Current consumption from integrated power supply – quiescent condition:
CSP-208 .......................................................................................................115 mA
CSP-204 .........................................................................................................80 mA
CSP-108 .......................................................................................................105 mA
CSP-104 .........................................................................................................75 mA
Current consumption from integrated power supply – fire alarm condition:
CSP-208 .......................................................................................................170 mA
CSP-204 .......................................................................................................140 mA
CSP-108 .......................................................................................................155 mA
CSP-104 .......................................................................................................130 mA
Zone number:
CSP-208 / CSP-108 ................................................................................................8
CSP-204 / CSP-104 ................................................................................................4
Maximum zone circuit resistance .................................................................... 100 Ω (2 x 50 Ω)
Maximum number of detectors in zone circuit........................................................................32
Maximum number of manual call points (MCPs) in zone circuit............................................. 10
End-of-line resistor in zone circuit ....................................................................... 5.6 k Ω +/- 5%