1-4 Introduction Date Code 20010518
SEL-2020 Instruction Manual
5. Set the computer terminal or emulation software to operate at:
2400 baud
8 data bits
1 stop bit
no parity
6. Press <ENTER> and verify that a “*” prompt is returned.
7. Type ACCESS<ENTER> to change to Access Level 1. Enter the factory-set password by
typing OTTER<ENTER> at the password prompt. You will see a screen similar to the
following:
*ACCESS<ENTER>
*ACCESS<ENTER>*ACCESS<ENTER>
*ACCESS<ENTER>
Password: ? OTTER<ENTER>
OTTER<ENTER>OTTER<ENTER>
OTTER<ENTER>
EXAMPLE 2020 - S/N 94153001 Date: 01/02/90 Time: 06:54:03
Level 1
*>
8. Type STATUS<ENTER> and verify that a status report similar to the one below appears on
your terminal. The RAM memory size should be 512 kb or 1024 kb. If you ordered optional
Flash memory, verify that Flash reports 2048 kb. If you did not order optional Flash
memory, Absent is reported as in the screen below. Confirm that IRIG-B input, I/O board,
and modem configurations match your expectations. The status and communications
statistics are shown for the 16 rear-panel ports and the front-panel port. Refer to the
STATUS command explanation in Section 5: Commands for more detailed information.