EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-251 - Disable Ground;Residual Overcurrent Elements with Block Trip Input

Schweitzer Engineering Laboratories SEL-251
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 20000421 Applications 5-9
SEL-251, -2, -3 Instruction Manual
Some applications may require that the permissive trip input supervise a low-set ground residual
instantaneous overcurrent element. In the following example, 79SH also supervises the low-set
ground/residual instantaneous overcurrent element 50NL in a fuse-saving scheme.
Using SELOGIC Control Equations:
A(12) = 51NT (ground/residual time-overcurrent element)
B(12) = 50NL (low-set ground residual instantaneous overcurrent element)
E(34) = 79SH
F(34) = IN5 (input IN5 will function as a permissive trip input)
V(56) = A*F
W(56) = B*E*F
TR(1246) = V+W+... (TR is the programmable trip condition)
effectively, TR(1246) = (51NT*IN5)+(50NL*79SH*IN5)+...
which reduces to: TR(1246) = [51NT+(50NL*79SH)]*IN5+...
close TRIP output contacts = TR+ ...
Disable Ground/Residual Overcurrent Elements with Block Trip Input
When a block trip input is energized, selected overcurrent elements are disabled for tripping.
When a block trip input is de-energized, selected overcurrent elements are enabled for tripping.
This function is the opposite of a permissive trip input.
Inputs IN5 and IN6 are available in the Relay Word and can be effectively used as block trip
inputs.
Using SELOGIC Control Equations:
A(12) = 51NT (ground/residual time-overcurrent element)
L(1234) = IN5 (input IN5 to function as a block trip input)
V(56) = A*!L (!L=NOT(L) = NOT(IN5))
TR(1246) = V+... (TR is the programmable trip condition)
effectively, TR(1246) = 51NT*NOT(IN5)+...
close TRIP output contacts = TR + ...
Some applications may require that the block trip input supervise a low-set ground residual
instantaneous overcurrent element. In the following example, 52AT also supervises the low-set
ground/residual instantaneous overcurrent element 50NL in a fuse-saving scheme.
Using SELOGIC Control Equations:
A(12) = 51NT (ground/residual time-overcurrent element)
B(12) = 50NL (low-set ground residual instantaneous overcurrent element)
E(34) = 52AT
L(1234) = IN5 (input IN5 will function as a block trip input)
V(56) = A*!L (!L=NOT(L) = NOT(IN5))
W(56) = B*E*!L
TR(1246) = V+W+... (TR is the programmable trip condition)

Table of Contents

Related product manuals