3-6 Communications Date Code 970103
SEL-251, -2, -3 Instruction Manual
=>2ACCESS <ENTER>
Password: TAIL <ENTER>
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:03:32
Level 2
=>>
You can enter any command at this prompt.
Command Format
Commands consist of three or more characters; only the first three characters of any command
are required. You may use upper or lower case characters without distinction, except in
passwords.
You must separate arguments from the command by spaces, commas, semicolons, colons, or
slashes.
You can enter commands any time after the terminal displays an appropriate prompt.
In this manual, commands to type appear in bold/upper case: OTTER. Keys to press appear in
bold/upper case/brackets: <ENTER>. Some commands have optional parameters; these appear
after the command in bold/lower case.
COMMAND DESCRIPTIONS
Access Level 0 Command
ACCESS
ACCESS allows you to enter Access Level 1. The password is required unless you install
jumper JMP103. The first password is set to OTTER at the factory; use the Level 2 command
PASSWORD to change passwords.
The following display indicates successful access:
=ACCESS <ENTER>ACCESS <ENTER>
Password: OTTER <ENTER>OTTER <ENTER>
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 14:03:57
Level 1
=>
The => prompt indicates Access Level 1.