3-14 Communications Date Code 970103
SEL-251, -2, -3 Instruction Manual
METER RP
METER RP resets peak demand values to their respective demand values.
=>METER RP <ENTER>METER RP <ENTER>
Reset Peak Demand: Are you sure (Y/N) ? Y <ENTER>Y <ENTER>
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 10:31:26
DEM IA=341 B=345 C=348 R=5
3I2=4 P=12.875 Q=0.757
PK IA=341 B=345 C=348 R=5
3I2=4 P=12.875 Q=0.757
=>
QUIT
QUIT returns control to Access Level 0 from Level 1 or 2 and resets targets to the Relay Targets
(TAR 0). The command displays the relay I.D., date, and time of QUIT command execution.
Use this command when you finish communicating with the relay to prevent unauthorized
access. Control returns to Access Level 0 automatically after a settable interval of no activity
(see the TIME1 and TIME2 settings of the SET command).
=>QUIT <ENTERQUIT <ENTER>
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:45:40
=
SHOWSET n
SHOWSET n displays the relay and logic settings for setting group n (n = 1, 2, 3, 4, 5, or 6).
You cannot enter or modify settings with this command. The SET command description
provides complete information about changing settings and logic. To display the active setting
group, execute SHOWSET without the parameter n.
The display also includes the global settings (settings common to all groups).
The SHOWSET output pauses twice, as shown in the following example. Press <ENTER> to
continue viewing the next section of settings.