EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-251 - Page 17

Schweitzer Engineering Laboratories SEL-251
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 20000421 Specifications 2-3
SEL-251, -2, -3 Instruction Manual
Environmental
Type Tests
IEEE C37.90-1989
IEEE Standards for Relays and Relay Systems Associated with Electrical Power
Apparatus, Section 8: Dielectric Tests
Severity Level: 2500 Vac on analog inputs; 3000 Vdc on power supply, contact
inputs and contact outputs
IEEE C37.90.1-1989
IEEE Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems
Severity Level: 3.0 kV oscillatory, 5.0 kV fast transient
IEEE C37.90.2 (Issued for trial use December 1987)
IEEE Trial-Use Standard, Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
Severity Level: 10 V/m
Exceptions:
5.5.2 (2) Performed with 200 frequency steps per octave
5.5.3 Digital Equipment Modulation Test not performed
5.5.4 Test signal turned off between frequency steps to simulate
keying
IEC 68-2-1 Fifth Edition - 1990
Environmental testing, Part 2: Tests - Test Ad: Cold
Severity Level: 16 hours at -40°C
IEC 68-2-2 Fourth Edition - 1974
Environmental testing, Part 2: Tests - Test Bd: Dry heat
Severity Level: 16 hours at +85°C
IEC 68-2-30 Second Edition - 1980
Basic environmental testing procedures, Part 2: Tests - Test Db and guidance:
Damp heat, cyclic (12 + 12-hour cycle)
Severity Level: 55°C, 6 cycles
IEC 255-5 First Edition - 1977
Electrical relays, Part 5: Insulation tests for electrical relays,
Section 6: Dielectric Tests
Severity Level: Series C (2500 Vac on analog inputs; 3000 Vdc on power
supply, contact inputs and contact outputs)
Section 8: Impulse Voltage Tests
Severity Level: 0.5 Joule, 5000 volt
IEC 255-21-1 First Edition - 1988
Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests
(sinusoidal)
Severity Level: Class 1
IEC 255-21-2 First Edition - 1988
Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section Two - Shock and bump tests
Severity Level: Class 1

Table of Contents