3-26 Communications Date Code 970103
SEL-251, -2, -3 Instruction Manual
52APU : 52A PU, cyc...............................................= 1200 ? 0-16000
Time delay pickup for 52AT
52ADO : 52A DO, cyc..............................................= 0 ? "
Time delay dropout for 52AT
TSPU : Tmr PU, cyc...............................................= 0 ? "
Timer TS time delay pickup (timer TS output is Relay Word bit ST)
TSDO : Tmr DO, cyc..............................................= 0 ? "
Timer TS time delay dropout (timer TS output is Relay Word bit ST)
TKPU :....................................................................= 0 ? "
Timer TK time delay pickup (timer TK output is Relay Word bit KT)
TKDO :....................................................................= 0 ? "
Timer TK time delay dropout (timer TK output is Relay Word bit KT)
TZPU :....................................................................= 0 ? "
Timer TZ time delay pickup (timer TZ output is Relay Word bit ZT)
TZDO :....................................................................= 0 ? "
Timer TZ time delay dropout (timer TZ output is Relay Word bit ZT)
Set remaining settings equal to combinations of elements in the Relay Word via SELOGIC
Control Equations. You can clear logic settings by entering NA.
The following settings S(123) through A2(1234) can be set to equal any OR-combination of
elements in the Relay Word rows indicated in parentheses.
S(123) = ? Input into timer TS (TS output is Relay Word bit ST)
Settings A(12) through J(1234) are for Relay Word bits A through J, respectively.
A(12) = ?
B(12) = 50NLT ?
C(12) = 50NL ?
D(12) = ?
E(34) = 79RS+79CY+52AT ?
F(34) = IN6 ?
G(34) = ?
H(34) = ?
J(1234) = ?
K(1234) = ? Input into timer TK (TK output is Relay Word bit KT)
L(1234) = ? Input into an inverter (output is Relay Word bit !L)
A1(1234) = TF ? A1 output contact setting
A2(1234) = NDEM ? A2 output contact setting