EasyManua.ls Logo

Seltron ST2 - Page 26

Seltron ST2
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
Heating optimisation: ST2 automatically calculates the switch-on
time and at setted time (night-day changeover) the requested
temperature is already reached.
Service group S2
settings. In program group S2 are the following parameters;
(Factory setting):
- [S2.1]
- [S2.2]
- [S2.3] Minimal temperature setting - limitation
- - - no limitation); (- - -)
- [S2.4] Maximal temperature setting - limitation
- - - no limitation); (- - -)
- [S2.5]
- [S2.6] P-
- [S2.7] Timer accuracy correction
(- (0 sec/day)
- [S2.8]
1
; (1)
- [S2.9]
1
; (1)
- [S2.10]
1
; (1)
SETTING MANUAL
26
- [S1.6]
Heating optimisation
1
(- - - deactivated, 1 - activated); (2)
- [S1.7] Controlling algorithm
(1 - P-controller, 2 - PI-controller); (P)
- [S1.8] Pre-setted time programs - selection (- - - no selection,
1 - fixed only, 2 - user programs only,
3 - fixed and user progr.); (3)
- [S1.9] Thermostat locking (- - - no locking, 1 - no locking, but
limited function of key , 2 - enabled key Party and knob,
3 - enabled only key Party, 4 - full lock); (2)
- [S1.10] Relay output timeout - delay (- - - (- - -)