EasyManua.ls Logo

SEW-Eurodrive MFE Series - Page 68

SEW-Eurodrive MFE Series
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Startup
Startup procedure
Manual – EtherCAT
®
Interfaces, Field Distributors
68
5. Make sure the screw plug of the setpoint potentiometer has a seal and screw it in.
NOTICE Loss of guaranteed degree of protection if the screw plugs on the f1 set-
point potentiometer and X50 diagnostic interface are not installed or not installed
correctly.
Damage to the MOVIMOT
®
inverter.
Make sure the screw plug of the setpoint potentiometer has a seal and screw it
in.
6.
3
4
5
6
7
8
Set minimum frequency f
min
with switch f2.
Function Setting
Detent setting 0 1 2 3 4 5 6 7 8 9 10
Minimum frequency f
min
[Hz]
2 5 7 10 12 15 20 25 30 35 40
7.
3
4
5
6
7
8
If the ramp time is not specified via the fieldbus (S1/2 DIP switch =
"ON"), set the ramp time at the t1 switch of the MOVIMOT
®
inverter.
The ramp time is based on a setpoint step change of 1500min
-1
(50Hz).
Function Setting
Detent setting 0 1 2 3 4 5 6 7 8 9 10
Ramp time t1 [s] 0.1 0.2 0.3 0.5 0.7 1 2 3 5 7 10
8. Check to see if the required direction of rotation on the MOVIMOT
®
inverter has
been enabled.
Terminal R Terminal L Meaning
Activated Activated
Both directions of rotation are enabled.
24V
R
L
Activated Not activated
Only CW rotation is enabled
Setpoint input for CCW rotation will stop the
drive.
24V
R
L
Not activated Activated
Only CCW rotation is enabled.
Setpoint input for CW rotation will stop the
drive.
24V
R
L
25809148/EN – 01/2019

Table of Contents

Related product manuals