Startup
Startup procedure
Manual – EtherCAT
®
Interfaces, Field Distributors
69
Terminal R Terminal L Meaning
notactivated Not activated
The device is inhibited or the drive is brought
to a stop.
24V
R
L
9. Set the S1/1 and S1/2 DIP switches on the MFE EtherCAT
®
interface according to
your system's requirements.
1
432
ON
S1
res. (OFF)
res. (OFF)
PD CONFIG (OFF)
I/O CONFIG (OFF)
8981582219
DIP
switch
Designation Meaning
S1/1 I/O CONFIG Configuration of digital inputs and outputs
OFF: 4 DI + 2 DO (factory setting)
ON: 6 DI
S1/2 PD CONFIG Configuration of process data transfer between MFE
EtherCAT
®
interface and MOVIMOT
®
OFF: 3 PD => higher-level controller ramp (factory
setting)
ON: 2 PD => ramp configuration on t1 DIP switch
of MOVIMOT
®
inverter
10. Place the MOVIMOT
®
inverter and the MFE housing cover on the field distributor
and screw them on.
11. Switch on the 24 V DC supply voltage for the MFE EtherCAT
®
interface and the
MOVIMOT
®
inverter.
Startup has been completed successfully when the MFE... fieldbus interface
shows the following.
The green "RUN" LED lights up.
The red "SYS-F" LED is not lit.
12. Configure the MFE EtherCAT
®
interface on the EtherCAT
®
master.
INFORMATION
In conjunction with EtherCAT
®
, no further settings are necessary on the drive.
EtherCAT
®
is configured entirely using software tools. For more information on the
configuration, refer to chapter "EtherCAT
®
configuration".