Manual – MOVI-PLC® advanced DHE41B/DHF41B/DHR41B Controller
4
Installing the MOVI-PLC® advanced DHR41B controller
Mounting/Installation Instructions
4.5.7 Setting the IP address parameters via DCP
Initial startup For PROFINET IO, the IP address parameters are determined via the "DCP" protocol
(Discovery and Configuration Protocol). DCP operates with device names (Device
Name). The device name uniquely identifies a PROFINET IO station in the network. It
is identified with the PROFINET IO controller for the project planning of the station and
also set using the project planning software on the PROFINET IO device. With the aid
of the device name, the controller identifies the device during startup and transfers the
corresponding IP address parameters. Settings directly on the slave are no longer re-
quired.
Resetting the IP
address parame-
ters
If you do not know the IP address parameters and cannot access the inverter using the
serial interface or the DBG60B keypad, you can reset the IP address parameters to the
default values using the DIP switch "2
0
".
This action resets the DHR41B option to the following default values:
IP address: 192.168.10.4
Subnetwork mask: 255.255.255.0
Default gateway: 1.0.0.0
PROFINET device name: PNETDeviceName_MACID
Proceed as follows to reset the IP address parameters to the default values:
Switch off the 24 V DC supply voltage and the mains voltage.
Set the DIP switch "2
0
" on the DHR41B option to "1".
Switch the DC 24 V supply voltage and the line voltage back on.
Wait until the DHR41B option has booted up. The "RUN" LED is green when the op-
tion is ready.
You can now access the inverter via the IP address 192.168.10.4. Proceed as follows
to set new IP address parameters:
Start MOVITOOLS
®
MotionStudio.
Select the address parameters you want.
Set the DIP switch "2
0
" on the DHR41B option to "0".
The new address parameters are adopted after the device is switched off and
switched on again.