Parameter Description
Total muting time 0 = infinite, 5 s … 3,600 s, adjustable in 1 s increments
"P
arameter Total muting time", page 104
Concurrency monitoring
t
ime
0 = infinite, 10 ms … 3,000 ms, adjustable in 10 ms increments.
If the value is not 0, it must be greater than the logic execution
time.
"Parameter Concurrency monitoring time", page 104
Suppression of sensor sig‐
nal gaps
0 = infinite, 10 ms ... 1,000 ms, adjustable in 10 ms increments.
If t
he value is not 0, it must be greater than the logic execution
time.
see "Parameter Suppression of sensor signal gaps", page 104
Additional muting time
af
ter the ESPE is released
0 ms, 200 ms, 500 ms, 1,000 ms
"Parameter Additional muting time after the ESPE is released",
page 105
Input C1
A
ctive
Deactivated
Override input
A
ctive
Deactivated
Conveyor
Active
Deactivated
Sequence/timing diagram
Figure 45: Sequence/timing diagram
7 C
ONFIGURATION
94
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact 8024589/2020-11-10 | SICK
Subject to change without notice

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Compact and is the answer not in the manual?

SICK Flexi Compact Specifications

General IconGeneral
BrandSICK
ModelFlexi Compact
CategoryController
LanguageEnglish

Related product manuals