OPERATING INSTRUCTIONS | LFP INOX 8019921/15H0 / 2019-09-30| SICK AG
Irrtümer und Änderungen vorbehalten
31
8OPERATION
8.2.6 Normally open with error signal
Application
If there is an error message on the LFP, this can be transferred using a switching con-
tact.
Conguration
1. Congure the Qx switching output as normally open.
Set the parameter in the QxMENU-OUx menu to Qx_Eno.
2. Select the electrical property [NPN/PNP/DRV (push/pull)]
Select the parameter in the QxMENU-TYPx menu.
Where the following applies:
Qx-PNP = Switching output in PNP circuit
Qx-NPN = Switching output in NPN circuit
Qx-Drv = Switching output in push/pull function
8.2.7 Normally closed with error signal
Application
If there is an error message on the LFP, this can be transferred using a switching con-
tact.
Conguration
1. Congure the Qx switching output as normally closed.
Set the parameter in the QxMENU-OUx menu to Qx_Enc.
2. Select the electrical property [NPN/PNP/DRV (push/pull)]
Select the parameter in the QxMENU-TYPx menu.
Where the following applies:
Qx-PNP = Switching output in PNP circuit
Qx-NPN = Switching output in NPN circuit
Qx-Drv = Switching output in push/pull function